Information identified as archived on the Web is for reference, research or recordkeeping purposes. It has not been altered or updated after the date of archiving. Web pages that are archived on the Web are not subject to the Government of Canada Web Standards. As per the Communications Policy of the Government of Canada, you can request alternate formats on the "Contact Us" page.

3.6.3.3.(5)
OS1OH2OP1OS1OP1OS1OP1OS1OP1
ObjectiveOP1 Fire Protection of the Building
Attribution
(c) [F01,F02-OP1.2]
Application
Application 1: 
Other uses of rooms and compartments where intake openings for linen chutes and refuse chutes are located, in buildings described in Sentence 1.3.3.2.(1) of Division A.
Application 2: 
This also applies to chutes and shafts in buildings to which Part 9 applies [see Sentence 1.3.3.3.(1) of Division A for application of Part 9], as stated in Sentence 9.10.1.2.(7), except where the chute or shaft is entirely contained within a dwelling unit.
Top of Page
Intent
Intent 1: 
To limit the probability of other fire hazards in a room or compartment where intake openings for a linen chute or a refuse chute are located, which could lead to a fire or the spread of fire to other parts of the building, which could lead to damage to the building.