Information identified as archived on the Web is for reference, research or recordkeeping purposes. It has not been altered or updated after the date of archiving. Web pages that are archived on the Web are not subject to the Government of Canada Web Standards. As per the Communications Policy of the Government of Canada, you can request alternate formats on the "Contact Us" page.
3.1.9.2.(1) | Application | Intent |
OS1 | + | OP1 |
Objective | OP1 Fire Protection of the Building |
Attribution |
[F03-OP1.2]
[F02,F04-OP1.3]
Applies to portion of Code text: “Except as permitted by Articles 3.1.9.3. and 3.1.9.4.,
pipes, ducts, electrical outlet boxes, totally enclosed raceways or other
similar service equipment that penetrate an assembly required to have a fire-resistance rating shall be noncombustible …”
|
Application | Application 1: Combustibility of pipes, ducts, electrical outlet
boxes, totally enclosed raceways or other similar service equipment that penetrate
an assembly required to have a fire-resistance rating,
in buildings described in Sentence 1.3.3.2.(1) of Division A.
Exceptions:
except:
|
Top of Page | |
Intent | Intent 1: To limit the probability that certain service equipment
that penetrates fire-rated assemblies will contribute to the growth and spread
of fire within the assemblies, which could lead to a structural failure and
collapse of the assemblies, which could lead to damage to the building.
Intent 2: To limit the probability that certain service equipment
that penetrates fire-rated assemblies--which also form a fire separation--will
contribute to the growth and spread of fire within the assemblies, which could
lead to a loss of integrity of the assemblies, which could lead to the spread
of fire and smoke from one fire compartment to another fire compartment, which
could lead to damage to the building in the other fire compartment.
|