Information identified as archived on the Web is for reference, research or recordkeeping purposes. It has not been altered or updated after the date of archiving. Web pages that are archived on the Web are not subject to the Government of Canada Web Standards. As per the Communications Policy of the Government of Canada, you can request alternate formats on the "Contact Us" page.
3.4.3.2.(6) | Application | Intent |
OS3 | + |
Application | Application 1: Required exit width for exit stairs that serve interconnected
floor spaces designed in accordance with Articles 3.2.8.3. to 3.2.8.9., where the stairs
provide not less than 0.3 m2 of area of treads
and landings for each occupant of the interconnected
floor spaces, or protected floor spaces conforming to Article 3.2.8.6. are
provided at each floor level and the protected floor space on a floor level
has not less than 0.5 m2 of space for each occupant
of that floor level of the interconnected floor space.
This applies to buildings described
in Sentence 1.3.3.2.(1) of Division A that contain portions of a floor area or mezzanines that
do not terminate at an exterior wall, a firewall or
a vertical shaft, and are required in Clause 3.2.8.1.(1)(b) to be protected
in conformance with Articles 3.2.8.3. to 3.2.8.9.
Application 2: This also applies to:
Exceptions:
except as stated in:
|
Top of Page | |
Intent | Intent 1: To supersede the requirement in the first part of Sentence 3.4.3.2.(6) that exit width be cumulative on the basis that an intermediate
area of safety is provided that allows persons to be protected from the hazards
of the interconnected floor space while queuing before entering an exit stair
or while waiting to proceed in the exit stair. |
Top of Page |