Information identified as archived on the Web is for reference, research or recordkeeping purposes. It has not been altered or updated after the date of archiving. Web pages that are archived on the Web are not subject to the Government of Canada Web Standards. As per the Communications Policy of the Government of Canada, you can request alternate formats on the "Contact Us" page.
3.4.3.2.(6) | Application | Intent |
OS3 | + |
Objective | OS3 Safety in Use |
Attribution | |
Application | Application 1: Required exit width for exit stairs that serve interconnected
floor spaces designed in accordance with Articles 3.2.8.3. to 3.2.8.9. This
applies to buildings described in Sentence 1.3.3.2.(1) of Division A that contain portions of a floor area or mezzanines that do not terminate at an exterior wall,
a firewall or a vertical shaft, and are required
by Clause 3.2.8.1.(1)(b) to be protected in conformance with Articles 3.2.8.3. to 3.2.8.9.
Application 2: This also applies to:
Exceptions:
except:
|
Top of Page | |
Intent | Intent 1: To supersede the permission of Sentence 3.4.3.2.(4) not
to cumulate exit widths for superimposed floor areas on the basis that all
floor areas in an interconnected floor space are subject to exposure from
the same fire or other untenable conditions and thus require simultaneous
exiting from all floors. This is to limit the probability
that exits will be of insufficient width to permit efficient egress simultaneously
from all portions of the interconnected floor space in an emergency situation,
which could lead to delays in the evacuation or movement of persons to a safe
place, which could lead to harm to persons.
|