Information identified as archived on the Web is for reference, research or recordkeeping purposes. It has not been altered or updated after the date of archiving. Web pages that are archived on the Web are not subject to the Government of Canada Web Standards. As per the Communications Policy of the Government of Canada, you can request alternate formats on the "Contact Us" page.

9.10.3.3.(2)
++
Application
Application 1: 
Compliance of exterior walls of buildings to the temperature rise limitations required by the standard tests referred to in Article 9.10.3.1., where:
  • such walls have a limiting distance of not less than 1.2 m, and
  • due allowance is made for the effects of heat radiation in accordance with the requirements in Part 3
This applies to buildings to which Part 9 applies [see Sentence 1.3.3.3.(1) of Division A for application of Part 9].
Top of Page
Intent
Intent 1: 
To exempt exterior walls from the temperature rise limitations required by the standard tests referred to in Article 9.10.3.1. if certain conditions are met [such walls have a limiting distance of not less than 1.2 m] and due allowance is made for the effects of heat radiation [e.g. Sentence 3.2.3.1.(6)] so as to limit the probability that fire will spread from one building to an adjacent building.
Intent 2: 
To expand the application of Sentence 3.2.3.1.(6) to Part 9 buildings.