Information identified as archived on the Web is for reference, research or recordkeeping purposes. It has not been altered or updated after the date of archiving. Web pages that are archived on the Web are not subject to the Government of Canada Web Standards. As per the Communications Policy of the Government of Canada, you can request alternate formats on the "Contact Us" page.
9.10.11.2.(3) | Application | Intent |
OS1 | OP3 |
Objective | OP3 Protection of Adjacent Buildings from Fire |
Attribution | |
Application | Application 1: Fire stopping of any spaces between the top of the
wall described in Sentence 9.10.11.2.(1) [party
walls on a property line between dwelling units,
where the wall is constructed as a fire separation having
not less than a 1 h fire-resistance rating ]
and the roof deck. This applies to buildings to
which Part 9 applies [see Sentence 1.3.3.3.(1) of Division A for application
of Part 9] that are of residential occupancy and
in which there is no dwelling unit above another dwelling unit.
|
Top of Page | |
Intent | Intent 1: To limit the probability that fire will spread through spaces
between the top of a party wall and a roof deck, which could lead to the spread
of fire into the roof deck from the building to an adjacent building, which
could lead to damage to the adjacent building. |
Top of Page |