Information identified as archived on the Web is for reference, research or recordkeeping purposes. It has not been altered or updated after the date of archiving. Web pages that are archived on the Web are not subject to the Government of Canada Web Standards. As per the Communications Policy of the Government of Canada, you can request alternate formats on the "Contact Us" page.

9.10.18.3.(3)
+OS1
ObjectiveOS1 Fire Safety
Attribution
[F02-OS1.2] Applies to the sprinklered building
[F11-OS1.5] Applies to the supervsion of the system and the flow alarm
Application
Application 1: 
Heat detectors and smoke detectors described in Sentence 9.10.18.3.(2) [heat detectors or smoke detectors in storage rooms, service rooms, elevator shafts, chutes, janitors' closets and any other rooms where hazardous substances are intended to be used or stored], in sprinklered buildings in which the sprinkler system is electrically supervised and equipped with a water flow alarm.
This applies to buildings to which Part 9 applies [see Sentence 1.3.3.3.(1) of Division A for application of Part 9] where fire alarm systems are required [see Article 9.10.18.2.].
Top of Page
Intent
Intent 1: 
To exempt buildings from the requirements of Sentence 9.10.18.3.(2), which would otherwise require heat or smoke detectors in certain spaces, if certain conditions are met [i.e. the building is sprinklered and the sprinkler system is electrically supervised and equipped with a water flow alarm].
This is to limit the probability that a fire will not be:
  • controlled or suppressed, which could lead to the growth and spread of fire, and
  • detected, which could lead to persons not being promptly notified of a fire situation.
This is to limit the probability of delays in the evacuation or movement of persons to a safe place, which could lead to harm to persons.