Information identified as archived on the Web is for reference, research or recordkeeping purposes. It has not been altered or updated after the date of archiving. Web pages that are archived on the Web are not subject to the Government of Canada Web Standards. As per the Communications Policy of the Government of Canada, you can request alternate formats on the "Contact Us" page.
9.21.1.2.(1) | Application | Intent |
OS1 | OH1 | OP1 |
Objective | OP1 Fire Protection of the Building |
Attribution | |
Application | Application 1: Flame-tightness of walls of chimneys and flue pipes, in buildings to
which Part 9 applies [see Sentence 1.3.3.3.(1) of Division A for application
of Part 9], where:
Exceptions:
except as stated in Sentence 9.21.1.1.(2), which applies to flue pipes serving gas-, oil- or solid-fuel-burning appliances that are covered by the standards referenced
in Sentences 9.33.5.2.(1) and 9.33.5.3.(1).
Application 2: This also applies to rectangular masonry
or concrete chimneys not more than 12 m in height that
serve fireplaces or appliances having a combined
total rated heat output of 120 kW or less, in buildings to
which Part 6 applies [see Sentence 1.3.3.2.(1) of Division A for application
of Part 6], as stated in Sentence 6.3.1.2.(1). |
Top of Page | |
Intent | Intent 1: To limit the probability that gaps or anomalies in chimneys
or flue pipes will lead to the escape of flames, which could lead to the ignition
of combustible building components, which could lead to damage to the building.
|