Information identified as archived on the Web is for reference, research or recordkeeping purposes. It has not been altered or updated after the date of archiving. Web pages that are archived on the Web are not subject to the Government of Canada Web Standards. As per the Communications Policy of the Government of Canada, you can request alternate formats on the "Contact Us" page.

9.21.4.9.(2)
OS2OH1OS3OS1
ObjectiveOS2 Structural Safety
Attribution
Application
Application 1: 
Prevention of the lateral displacement of flue liners in the same rectangular chimney of brick masonry or concrete, which is not more than 12 m in height and serves fireplaces or appliances having a combined total rated heat output of 120 kW or less, in buildings to which Part 9 applies [see Sentence 1.3.3.3.(1) of Division A for application of Part 9].
Application 2: 
This also applies to rectangular masonry or concrete chimneys, in buildings to which Part 6 applies [see Sentence 1.3.3.2.(1) of Division A for application of Part 6], as stated in Sentence 6.3.1.2.(1).
Top of Page
Intent
Intent 1: 
To limit the probability that joints between flue liner sections will open, which could lead to the leakage of condensate and combustion products into the surrounding masonry, which could lead to the structural damage and collapse of the chimney due to corrosion or freeze-thaw stresses, which could lead to harm to persons.