Information identified as archived on the Web is for reference, research or recordkeeping purposes. It has not been altered or updated after the date of archiving. Web pages that are archived on the Web are not subject to the Government of Canada Web Standards. As per the Communications Policy of the Government of Canada, you can request alternate formats on the "Contact Us" page.

9.23.3.4.(2)
OS2OP2OH1OS1OH4OS3
ObjectiveOS1 Fire Safety
Attribution
[F20,F22-OS1.2] Applies to assemblies required to provide fire resistance.
Application
Application 1: 
Fastening of lumber exterior-wall framing to lumber floor framing, in wood-frame constructions to which Section 9.23. applies [see Sentence 9.23.1.1.(1) for application of Section 9.23.], where the sole plate is not fastened to the floor joists or blocking with nails at least 82 mm long spaced not more than 400 mm o.c.
Top of Page
Intent
Intent 1: 
To limit the probability of inadequate fastening or an excessive rate of deterioration of fasteners, which could lead to an inability to resist expected wind loads, which could lead to the separation of exterior walls or wall elements from floors, which could lead to overturning, lifting or sliding of exterior walls.
Where assemblies are required to provide fire resistance, this is to limit the probability of compromised fire resistance of the assembly, which could lead to harm to persons.
Intent 2: 
To exempt situations from the application of Sentence 9.23.3.4.(1) where another means of fastening the wall framing to the floor framing is provided.