Information identified as archived on the Web is for reference, research or recordkeeping purposes. It has not been altered or updated after the date of archiving. Web pages that are archived on the Web are not subject to the Government of Canada Web Standards. As per the Communications Policy of the Government of Canada, you can request alternate formats on the "Contact Us" page.

9.32.3.1.(1)
OS3OH1
ObjectiveOH1 Indoor Conditions
Attribution
Application
Application 1: 
Heating-season mechanical ventilation systems serving single dwelling units that are supplied with electrical power and a heating system, in buildings to which:
  • Part 9 applies [see Sentence 1.3.3.3.(1) of Division A for application of Part 9], or
  • Part 6 applies [see Sentence 1.3.3.2.(1) of Division A for application of Part 6 and Sentence 6.2.2.1.(3)].
Top of Page
Intent
Intent 1: 
To limit the probability that the performance of heating-season mechanical ventilation systems will fall significantly below expectations.
This is to limit the probability of:
  • inadequate ventilation, or
  • the inadequate control of relative humidity.
This is to limit the probability of the inadequate control of:
  • indoor air temperatures,
  • airborne pollutants,
  • oxygen and other components necessary for breathable air, or
  • condensation, which could lead to the generation of pollutants from biological growth or from materials that become unstable on wetting.
This is to limit the probability of:
  • negative effects on the air quality of indoor spaces, or
  • the inadequate thermal comfort of persons.
This is to limit the probability of harm to persons.
Intent 2: 
[Clause (a)] To direct Code users to good practice options, such as those contained in CAN/CSA-F326-M, for the design of heating-season mechanical ventilation systems.
Intent 3: 
[Clause (b)] To state the application of Subsection 9.32.3., which contains requirements for heating-season mechanical ventilation systems in dwelling units with 5 or fewer bedrooms.