Information identified as archived on the Web is for reference, research or recordkeeping purposes. It has not been altered or updated after the date of archiving. Web pages that are archived on the Web are not subject to the Government of Canada Web Standards. As per the Communications Policy of the Government of Canada, you can request alternate formats on the "Contact Us" page.
4.3.7.2.(1) | Application | Intent |
OS1 | OS1 | OS1 | OP1 | OP1 | OH5 | OP1 | OH5 |
Objective | OP1 Fire Protection of the Building or Facility |
Attribution | |
Application | Application 1: Material for bases and walls of secondary spill containments
for aboveground storage tanks--and portable tanks
that have a capacity greater than 2 500 L [as stated in Sentence 4.2.1.1.(3)]--for flammable liquids and combustible liquids, in buildings,
structures and open areas.
Exceptions:
except:
|
Top of Page | |
Intent | Intent 1: To limit the probability that fire exposure will lead to
failure of the secondary containment, which could lead to the escape and spread
of liquid outside of the secondary containment, which could lead to the ignition
of vapour from a nearby ignition source, which could lead to damage to the
building or facility. |