Information identified as archived on the Web is for reference, research or recordkeeping purposes. It has not been altered or updated after the date of archiving. Web pages that are archived on the Web are not subject to the Government of Canada Web Standards. As per the Communications Policy of the Government of Canada, you can request alternate formats on the "Contact Us" page.
4.3.7.2.(1) | Application | Intent |
OS1 | OS1 | OS1 | OP1 | OP1 | OH5 | OP1 | OH5 |
Objective | OP1 Fire Protection of the Building or Facility |
Attribution | |
Application | Application 1: Design, construction and maintenance of bases and
walls of secondary spill containments for aboveground storage
tanks--and portable tanks that have a capacity greater than 2
500 L [as stated in Sentence 4.2.1.1.(3)]--for flammable
liquids and combustible liquids, in buildings, structures and open areas.
Exceptions:
except:
|
Top of Page | |
Intent | Intent 1: To limit the probability of liquid seepage through the secondary
containment, which could lead to the escape and spread of liquid outside of
the secondary containment, which could lead to the ignition of vapour from
a nearby ignition source, which could lead to damage to the building or facility.
|
Top of Page |