Information identified as archived on the Web is for reference, research or recordkeeping purposes. It has not been altered or updated after the date of archiving. Web pages that are archived on the Web are not subject to the Government of Canada Web Standards. As per the Communications Policy of the Government of Canada, you can request alternate formats on the "Contact Us" page.

4.3.10.3.(4)
OS1OS1OH5OH5
ObjectiveOS1 Fire Safety
Attribution
[F11-OS1.1] Applies to portion of Code text: “… except when the vent is equipped with a vent alarm.”
Application
Application 1: 
Entry location of normal vent piping equipped with a vent alarm, for underground storage tanks for flammable liquids or combustible liquids.
Exceptions: 
except as exempted in Sentences 4.1.1.1.(2) and (3), which apply to unique hazards at process plants, in transportation, for oil burning equipment, on farms and isolated construction projects, and the storage of aerosol products.
Top of Page
Intent
Intent 1: 
To remove the limitation on the extension of the vent piping into the tank [as stated in the beginning of Sentence 4.3.10.3.(4)] and permit vent piping to extend beyond this limitation if the vent is equipped with a vent alarm that will alert trained personnel of any vent obstruction.
This is to limit the probability that blocking or obstruction of the vent pipe by liquid will lead to overpressurization or back pressure, which could lead to failure of the tank and the escape of liquid--or blowback of liquid or vapour at the fill opening--which could lead to the ignition of vapour from a nearby ignition source, which could lead to harm to persons.