Information identified as archived on the Web is for reference, research or recordkeeping purposes. It has not been altered or updated after the date of archiving. Web pages that are archived on the Web are not subject to the Government of Canada Web Standards. As per the Communications Policy of the Government of Canada, you can request alternate formats on the "Contact Us" page.

4.3.10.3.(4)
OS1OS1OH5OH5
ObjectiveOH5 Hazardous Substances Containment
Attribution
[F20,F81-OH5] Applies to portion of Code text: “Vent piping shall enter the storage tank through the top of the tank and shall not extend into the tank more than 25 mm …”
Application
Application 1: 
Entry location and maximum extension into the tank of normal vent piping for underground storage tanks for flammable liquids or combustible liquids.
Exceptions: 
except:
  • when the vent is equipped with a vent alarm, and
  • as exempted in Sentences 4.1.1.1.(2) and (3), which apply to unique hazards at process plants, in transportation, for oil burning equipment, on farms and isolated construction projects, and the storage of aerosol products.
Top of Page
Intent
Intent 1: 
To limit the probability that blocking or obstruction of the vent pipe by liquid will lead to overpressurization or back pressure, which could lead to failure of the tank and the escape of liquid--or blowback of liquid at the fill opening--which could lead to harm to the public.