This information has been archived because it is outdated and no longer relevant.
Information identified as archived on the Web is for reference, research or recordkeeping purposes. It has not been altered or updated after the date of archiving. Web pages that are archived on the Web are not subject to the Government of Canada Web Standards. As per the Communications Policy of the Government of Canada, you can request alternate formats on the "Contact Us" page.
4.3.10.3.(4) | Application | Intent |
OS1 | OS1 | OH5 | OH5 |
Objective | OH5 Hazardous Substances Containment |
Attribution |
[F20,F81-OH5]
Applies to portion of Code text: “Vent piping shall enter
the storage tank through the top of the tank
and shall not extend into the tank more than 25 mm …”
|
Application | Application 1: Entry location and maximum extension into the tank
of normal vent piping for underground storage tanks for flammable liquids or combustible
liquids.
Exceptions:
except:
|
Top of Page | |
Intent | Intent 1: To limit the probability that blocking or obstruction of
the vent pipe by liquid will lead to overpressurization or back pressure,
which could lead to failure of the tank and the escape of liquid--or blowback
of liquid at the fill opening--which could lead to harm to the public.
|
Top of Page |