Information identified as archived on the Web is for reference, research or recordkeeping purposes. It has not been altered or updated after the date of archiving. Web pages that are archived on the Web are not subject to the Government of Canada Web Standards. As per the Communications Policy of the Government of Canada, you can request alternate formats on the "Contact Us" page.

5.5.4.3.(1)
OS1OP1OP1OP1OS1OS1OS1OS1
ObjectiveOP1 Fire Protection of the Building or Facility
Attribution
(b) [F02-OP1.2]
Application
Application 1: 
Air velocity in exhaust ventilation systems for power-ventilated enclosures, where, as stated in Sentence 5.5.4.2.(1):
  • the use of the dangerous goods releases flammable vapours, or causes runaway or potentially explosive reactions,
  • liquids are heated to a temperature equal to or greater than their flash point, or
  • Class I liquids or unstable liquids are used.
This applies to laboratories where dangerous goods, including flammable liquids and combustible liquids, are used in normal laboratory operations in quantities or in a manner that creates a fire or explosion hazard.
Application 2: 
This also applies where perchloric acid is heated above normal ambient temperature, as stated in Sentence 5.5.5.5.(1).
Top of Page
Intent
Intent 1: 
To limit the probability that combustible or reactive deposits will accumulate, which could lead to an increase of the combustible content and fire severity, which could lead to the spread of a fire in the laboratory to other parts of the building, which could lead to damage to the building.
Top of Page