Information identified as archived on the Web is for reference, research or recordkeeping purposes. It has not been altered or updated after the date of archiving. Web pages that are archived on the Web are not subject to the Government of Canada Web Standards. As per the Communications Policy of the Government of Canada, you can request alternate formats on the "Contact Us" page.

5.5.4.3.(1)
OS1OP1OP1OP1OS1OS1OS1OS1
ObjectiveOP1 Fire Protection of the Building or Facility
Attribution
(a) [F02-OP1.2]
Application
Application 1: 
Construction of exhaust ventilation systems for power-ventilated enclosures, where, as stated in Sentence 5.5.4.2.(1):
  • the use of the dangerous goods releases flammable vapours, or causes runaway or potentially explosive reactions,
  • liquids are heated to a temperature equal to or greater than their flash point, or
  • Class I liquids or unstable liquids are used.
This applies to laboratories where dangerous goods, including flammable liquids and combustible liquids, are used in normal laboratory operations in quantities or in a manner that creates a fire or explosion hazard.
Application 2: 
This also applies where perchloric acid is heated above normal ambient temperature, as stated in Sentence 5.5.5.5.(1).
Exceptions: 
except as stated in Clauses 5.5.4.4.(1)(a) and (b), and Sentences 5.5.4.4.(2) and (3), which apply to enclosure construction and combustibility.
Top of Page
Intent
Intent 1: 
To limit the probability that combustible construction will increase fire severity, which could lead to the spread of a fire to other parts of the building, which could lead to damage to the building.