Information identified as archived on the Web is for reference, research or recordkeeping purposes. It has not been altered or updated after the date of archiving. Web pages that are archived on the Web are not subject to the Government of Canada Web Standards. As per the Communications Policy of the Government of Canada, you can request alternate formats on the "Contact Us" page.
2.2.3.1.(2) | Application | Intent |
OH1 |
Objective | OH1 Indoor Conditions |
Attribution | |
Application | Application 1:
|
Top of Page | |
Intent | Intent 1: To modify the requirements of Sentence 2.2.3.1.(1) [specifically Clause 2.2.3.1.(1)(a)], which would otherwise permit a lesser
depth, on the basis that a greater minimum trap seal depth will provide additional
protection where exposure to acid gases is possible in an acid waste system.
This [greater seal depth] is to limit the probability that inertia of the
water flow [pressure differential] and evaporation, or malfunction of mechanical
devices, will lead to the failure of trap seals, which could lead to the leakage
of sewer gases into the building, which could lead to a negative effect on
indoor air quality, which could lead to harm to persons. |