Information identified as archived on the Web is for reference, research or recordkeeping purposes. It has not been altered or updated after the date of archiving. Web pages that are archived on the Web are not subject to the Government of Canada Web Standards. As per the Communications Policy of the Government of Canada, you can request alternate formats on the "Contact Us" page.

2.5.7.7.(1)
OH2
ObjectiveOH2 Sanitation
Attribution
Application
Application 1: 
Minimum size for vent pipes for sewage sumps, in drainage systems and venting systems for buildings.
Exceptions: 
except as stated in:
  • Sentence 2.5.7.7.(2), which applies to the minimum size of vent pipes for sewage sumps, and
  • Sentence 2.5.7.7.(3), which applies to the minimum size of vent pipes for macerating toilets.
Top of Page
Intent
Intent 1: 
To limit the probability that an inadequate vent size will lead to restricted air flow from sumps when waste water is flowing toward sumps, which could lead to airlock, which could lead to flow restriction of waste, which could lead to backups, which could lead to the entry of sewage or contaminated water into occupied space, which could lead to unsanitary conditions, which could lead to harm to persons.
Top of Page