Sentence 3.2.7.9.(2)

  1. OS1
  2. OP1
  3. OS3

Objective

OS1 Fire Safety

Attribution

Intent

Intent 1:

To limit the probability that, during a failure of the normal power supply in a fire emergency situation, emergency generator power supplies to elevators will not be capable of performing their intended functions for a length of time sufficient for emergency responders to carry out their duties, which could lead to the inability of elevator systems to be used in emergency response operations, which could lead to delays in emergency response operations, which could lead to:

  • delays in the evacuation or movement of persons to a safe place, which could lead to harm to persons, including emergency responders, and
  • the spread of fire, which could lead to harm to persons.

Intent 2:

To clarify that the emergency generator power supply required by Clause 3.2.7.9.(1)(a) is required to simultaneously operate all elevators for firefighters plus one additional elevator for recall.