Sentence 6.5.1.3.(1)

  1. OP1
  2. OS1
  3. OP3
  4. OS3

Objective

OS1 Fire Safety

Attribution

Intent

Intent 1:

To limit the probability that emergency responders will not be able to [manually] start, or will be delayed in [manually] starting, an emergency power system and to switch on essential loads when there is a failure of the system to start automatically in a fire situation, which could lead to the inability of the emergency power systems to supply fire protection systems, which could lead to the inability of:

  • fire alarm or voice communication systems to promptly notify persons in the building, which could lead to delays in the evacuation or movement of persons to a safe place,
  • sprinkler, standpipe and hose systems, and other fire suppression systems [that rely on booster or fire pumps, or electrical power] to control or suppress a fire, which could lead to the spread of fire,
  • emergency lighting systems to illuminate egress routes, which could lead to delays in the evacuation or movement of persons to a safe place,
  • smoke management systems to control smoke conditions as originally intended, which could lead to delays in emergency response operations, which could lead to delays in the evacuation or movement of persons to a safe place, and
  • elevator systems to be used in emergency response operations, which could lead to delays in emergency response operations, which could lead to delays in the evacuation or movement of persons to a safe place.

This is to limit the probability of harm to persons.

Intent 2:

To supersede the requirements of Sentence 6.5.1.1.(1).