Information identified as archived on the Web is for reference, research or recordkeeping purposes. It has not been altered or updated after the date of archiving. Web pages that are archived on the Web are not subject to the Government of Canada Web Standards. As per the Communications Policy of the Government of Canada, you can request alternate formats on the "Contact Us" page.
5.3.1.4.(3) | Application | Intent |
OS1 | OP1 | OS1 | OS1 |
Objective | OS1 Fire Safety |
Attribution | |
Application | Application 1: Recirculation or return to the building of
air from dust collectors referred to in Article 5.3.1.3. that have
a capacity greater than 0.5 m3/s.
This applies to buildings or parts of buildings where combustible dusts are
produced in quantities or concentrations that create an explosion or fire
hazard.
|
Top of Page | |
Intent | Intent 1: To permit exhaust air to return to the building if measures
are taken that would limit the probability that ignitable concentrations of
dusts will return into the building, which could lead to a fire or explosion
in the dust collecting system, which could lead to harm to persons.
|