Information identified as archived on the Web is for reference, research or recordkeeping purposes. It has not been altered or updated after the date of archiving. Web pages that are archived on the Web are not subject to the Government of Canada Web Standards. As per the Communications Policy of the Government of Canada, you can request alternate formats on the "Contact Us" page.

5.3.1.4.(3)
OS1OP1OS1OS1
ObjectiveOS1 Fire Safety
Attribution
(b) [F03-OS1.2]
Application
Application 1: 
Recirculation or return to the building of air from dust collectors referred to in Article 5.3.1.3. that have a capacity greater than 0.5 m3/s.
This applies to buildings or parts of buildings where combustible dusts are produced in quantities or concentrations that create an explosion or fire hazard.
Application 2: 
This also applies to dry powder spray coating operations covered in Sentence 5.4.5.2.(1).
Top of Page
Intent
Intent 1: 
To limit the probability that a fire or explosion inside a dust collector will spread beyond the dust collector and inside the building, which could lead to harm to persons.