Sentence 9.10.18.4.(3)

  1. +
  2. OS1

Objective

OS1 Fire Safety

Attribution

[F11-OS1.5]Applies to the supervision of the system and the flow alarm.

Intent

Intent 1:

To exempt buildings from the requirements of Sentence 9.10.18.4.(2), which would otherwise require heat or smoke detectors in certain spaces, if certain conditions are met [i.e. the building is sprinklered and the sprinkler system is electrically supervised and equipped with a water flow alarm].

This is to limit the probability that a fire will not be:

  • controlled or suppressed, which could lead to the growth and spread of fire, and
  • detected, which could lead to persons not being promptly notified of a fire situation.

This is to limit the probability of delays in the evacuation or movement of persons to a safe place, which could lead to harm to persons.