Information identified as archived on the Web is for reference, research or recordkeeping purposes. It has not been altered or updated after the date of archiving. Web pages that are archived on the Web are not subject to the Government of Canada Web Standards. As per the Communications Policy of the Government of Canada, you can request alternate formats on the "Contact Us" page.

9.3.1.6.(1)
OS2OP2OH1OH4OS3OS1OS2OP2OH1OS3OS2OP2OS3
ObjectiveOH1 Indoor Conditions
Attribution
Application
Application 1: 
Minimum compressive strength of cast-in-place concrete that is not required to be reinforced that is used for floors, in buildings to which Part 9 applies [see Sentence 1.3.3.3.(1) of Division A for application of Part 9].
Exceptions: 
except as stated in Clause 9.3.1.6.(1)(c), which applies to concrete for garage and carport floors where exposure to de-icing salts, water from rain or melting snow, freezing and thawing stresses, traffic, abrasion or other severe exposure conditions is likely.
Top of Page
Intent
Intent 1: 
To limit the probability of:
  • insufficient compressive strength to resist expected gravity loads, or
  • the excessive shrinkage, cracking and premature failure of concrete.
Where concrete is used in an environmental separator, this is to limit the probability of:
  • the compromised integrity of the environmental separation elements, or
  • an inadequate resistance to air and moisture transfer through the concrete.
This is to limit the probability of:
  • pollutant ingress (from the exterior, including soil gas)
  • condensation,
  • the ingress of moisture from the ground, or
  • the compromised thermal performance of components intended to provide resistance to heat transfer.
This is to limit the probability of:
  • the generation of pollutants from biological growth or from materials that become unstable on wetting,
  • deterioration, which could lead to further compromised integrity of environmental separators, or
  • an inadequate control of indoor air and surface temperatures, drafts, relative humidity, or water accumulation.
This is to limit the probability of:
  • negative effects on the air quality of indoor spaces,
  • the inadequate thermal comfort of persons, and
  • contact with moisture.
This is to limit the probability of harm to persons.